• Make sure the terminals in the box are not under power (Use shielded cable 7 x 0.5 mm2 (20 AWG) – with relay output, 4 x 0.5 mm2 – without relay output suggested in the technical data or stronger).
  • After powering the necessary programming can be performed.

Wire colours:

Pink – relay C1 output   White – I, one of the points of current loop, power supply and HART (polarity independent)

Grey – relay CC output   Brown – I, other point of current loop, power supply and HART (polarity independent)

Blue – relay C2 output   Black – GND, functional earthing and shielding point

Extension of the integrated cable:

Should extension be needed the use of connection box is suggested. The shielding of the two cables should be connected and grounded at the signal processing device.