The single-phase UPS for critical applications
ABB’s PowerValue11RT G2 is a double-conversion online UPS that guarantees up to 10 kW of clean, reliable power for your critical single-phase applications. As well as maintaining power to your servers, point-of-sale terminals, workstation clusters, routers, switches, hubs and sensitive electronic equipment, the PowerValue11RT G2 also conditions incoming power to eliminate spikes, swells, sags, noise and harmonics.
The PowerValue11RT G2 can be used as a standalone UPS device or installed into a standard 19"rack configuration, with connectivity options available for each.
Three units of the 6 or 10kW models can be configured in parallel to provide redundancy or to increase the system's total capacity up to 30 kW. All units can be fitted with up to nine battery modules to extend runtime.
High reliability
- Reliable double conversion topology protects load from all input disturbances
- Batteries can be added or replaced easily
- Reduced recovery time from discharge
- Redundant parallel operation available (6 and 10kW units)
Flexible design
- Configurable in tower or rack-mount format
- Rotatable display
- UPS can be connected with up to nine external battery modules (EBMs) for extended runtime
- Long backup models available
- Full set of accessories and connectivity options
Low cost of ownership
- Unity power factor (kW = kVA)
- Scalable runtime
- High operating efficiency, regardless of loading
- Reduced installation and upgrading costs
- Compact design
Efficient service concept
- Manually operated maintenance bypass switch (optional)
- Easy set-up and maintenance (plug-and-play)
- User-friendly display
- Hot-swap user-replaceable internal batteries
Product features
Scalable solution
The advanced system architecture guarantees that the user is able to select a system to match their needs. Scalable runtime and the easy introduction of additional batteries make the solution sustainable.
In addition, three PowerValue11RT G2 6 or 10kW UPSs can be connected in parallel to increase total power or to add redundancy. The UPSs are delivered with an installed parallel board and paralleling cables. No additional hardware is required for a parallel installation.
Easy installation and maintenance
Ease of installation and operation is guaranteed. The 1-3 kVA module is a plug-n-play device where all you need to do is to plug it in a wall socket to begin protection. The 6-10 kVA UPS only requires basic electronic competence to properly start up the unit.
Both models have a versatile orientation (rack or tower), just by rotating the display; for 1-3 kVA UPS this is as easy as pushing a button. Mechanical accessories for securing the installation in standard 19'' racks or in a vertical position are included in each UPS.
Complete product offering
PowerValue 11RT G2 comes as a complete offering. For the range 1-3 kVA, B and S models are available. B models include internal batteries for basic runtime applications; however external battery modules (EBMs) can be plugged in to extend the system backup. S models have no internal batteries but a more powerful battery charger to support runtime-demanding applications; up to nine external battery modules (EBMs) or third-party battery packs (adapter included in the UPS) can be connected to form a personalized battery capacity.
The 6-10 kVA UPS integrates a max 12 A battery charger to withstand the most demanding scenarios and to support high-capacity battery extensions. A comprehensive set of accessories and options is available, too: External battery modules (EBMs), external maintenance bypass with PDU, 1U automatic transfer switch (ATS), rail kits for rack mounting, relay card with additional I/O potential-free contacts and full connectivity suite are available to complete the installation. Finally, optional yearly warranty extensions to the comprehensive basic warranty of three years allow peace of mind throughout the whole life cycle of the UPS
Available models
1 AC input 10 A |
2 USB port |
3 RS-232 |
4 SNMP/AS400 slot |
5 EPO/dry contact input port |
6 Dry contact output port |
7 AC output 10A |
8 AC input 16A |
9 AC input 20 A |
10 AC output 16A |
11 EPO |
12 Parallel port |
13 Dry in / out |
14 MBP connector |
15 Output breaker |
16 I/O terminals |
17 Input breaker |
18 EBM connector |
Options
- Rack installation kit allows for easy mounting in standard 19'' rack
- Full-range connectivity: SNMP, ModBus (RS-485 and TCP/IP), environmental monitoring probe, relay card with I/O contacts
- External maintenance bypass
- 1U automatic transfer switch (ATS) (PowerValue 11RT G2 1-3 kVA)
- High capacity external battery modules (EBMs) to scale up the system runtime (a plug-and-play cable included to connect UPS and other battery modules)
UPS configuration
- Online double conversion UPS
- Unity power factor (kW = kVA)
- Efficiency in online mode up to 95%
- Efficiency in eco-mode up to 98%
- Configurable in tower format or rack-mount
- Three 6 kVA and 10 kVA UPSs (max 30 kW per system) can be connected in parallel for redundancy or extra capacity
- Cold start
- Frequency-converter operation (50Hz or 60Hz)
- Interfaces: USB, RS-232, potential-free contacts, EPO
- Load segmentation (for PowerValue 11RT G2 1-3 kVA)
Technical specification
GENERAL DATA | 1kW B/ S | 2kW B/ S | 3kW B/ S | 6 kW | 10 kW |
Output rated power | 1,000 W | 2,000 W | 3,000 W | 6,000 W | 10,000 W |
Output power factor | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Topology | Online double conversion | ||||
Parallel configuration | No | No | No | Yes, up to 3 UPS | Yes, up to 3 UPS |
Inbuilt batteries | Yes/No | Yes/No | Yes/No | No | No |
INPUT | |||||
Nominal input voltage | 208/220/230/240 VAC | ||||
Input voltage tolerance | 120-300 VAC (load dependent) | 100-276 (load dependent) | |||
Input current THD | <5% with full resistive load | <3% with full resistive load | |||
Frequency range | 45-55 Hz / 54-66 Hz | 45-55 Hz / 54-66 Hz (extendable to 40~70 HZ at load < 60 %) | |||
Power factor | ≥0.99 | ≥0.995 | |||
OUTPUT | |||||
Rated output voltage | 208/220/230/240 VAC | ||||
Voltage tolerance | ±1 % (referred to 230V) | ||||
Voltage distortion | < 2 % linear load, <5 % non-linear load | < 1 % linear load, <5 % non-linear load | |||
Overload capacity (linear load) on inverter | 60 s: 102-129 % load 10 s: 130-150 % load 300 ms: ≥ 150 % load |
10 m: 102-125 % load 30 s: 126 to 150 % load 500 ms: ≥ 150 % load |
|||
Nominal frequency | 50 or 60 Hz | ||||
Crest factor | 3:1 (load supported) | ||||
EFFICIENCY | |||||
Overall system efficiency | Up to 92 % | Up to 95 % | |||
In eco-mode | Up to 98 % | Up to 98 % | |||
ENVIRONMENT | |||||
Protection rating | IP20 | ||||
Storage temperature | UPS: -25 °C to 60 °C; batteries: 0 °C to 35 °C | ||||
Operating temperature | 0 °C to 40 °C | ||||
Relative humidity | 0 % to 95 % | ||||
Altitude (above sea level) | 1000 m without derating | ||||
BATTERIES | |||||
Type | VRLA(valve regulated lead-acid) | ||||
Inbuilt batteries | 2x9.4 Ah | 4x9.4 Ah | 6x9.4 Ah | - | - |
Max charging current | 1.5 A/6 A | 1.5 A/6 A | 1.5 A/6 A | 0-12 A adjustable | |
COMMUNICATIONS | |||||
User interface | LCD | ||||
Optional communication cards | SNMP; ModBus; AS400; Environmental monitoring sensor probe | ||||
STANDARDS | |||||
Safety | IEC/EN 62040-1 | ||||
EMC | IEC/EN 62040-2 | ||||
Performance | IEC/EN 62040-3 | ||||
Manufacturing | ISO 9001:2015, ISO 14001:2015, OHSAS 18001 | ||||
WEIGHT, DIMENSIONS | |||||
Weight | 11.4/5.8 kg | 18.1/8.7 kg | 27.9/9 kg | 13.6 kg | 15.5 kg |
Dimensions w x h x d | 438x86(2U) x309 mm | 438x86(2U) x426 mm | 438x86(2U) x629 mm | 438x86(2U) x573 mm | 438x86(2U) x573 mm |